Message Description Advices
No parameter se-
lected
A recording has been started without
selecting values to be recorded
Push START/STOP, and se-
lect at least one value from
the MENU
No Phase selected Voltage and/or current harmonics have
been selected and the corresponding
flag has been enabled (HARMONICS
ON) but no phase voltage or current has
been selected
Select at least one phase
voltage and/or current
PASSWORD ERROR The password entered is wrong Insert the password: F1, F4,
F3, F2
PASSWORD OK The password is correct
Please wait The instrument is waiting for the record-
ing to start
Recording The instrument is recording
Too many param More than 63 parameters have been
selected (harmonics included) or more
than 38 parameters with COGENERA-
TION Flag enabled
Deselect parameters
Too many record The quantity of recorded data + Smp
exceeds the maximum allowed (35)
Transfer recordings to a PC
and then clear the instru-
ment memory
ERR: SEQ The Phase Sequence is wrong. Check the Phase Sequence
connection.
ERR: P- The active powers on the right side of
the message are negative
Check if the clamps are
properly connected, unless
co-generation is involved
ERR: SEQ & P- The active powers on the right side of
the message are negative and the Phase
Sequence is wrong.
Check if the clamps are
properly connected / check
the Phase Sequence con-
nection, unless co-genera-
tion is involved
ERR: CONNECTION The Voltage inputs are not connected
correctly.
Check the Voltage connec-
tions (see Physical Connec-
tions, Page X8)
Error Vref A Voltage reference was selected that is
not compatible with voltage input.
Check Voltage Reference
set in RECORDER CONFIG
in MENU
Error1 to Error 5 The instrument memory is damaged. Contact Amprobe for as-
sistance