4.1.2.1. Mode "AUTO"
)
CAL LOWΩ
.07 Ω
219 mA
AUTO
At the end of the test, if the average
resistance value Ravg
is less than 5Ω
the instrument emits a double beep
indicating the positive outcome of the
test and displays a screen similar to the
screen alongside.
verage test
current value
Iavg.
Average
resistance value
Ravg.
SAVE
SAVING
: The test results can be stored pressing the SAVE key twice
(refer to paragraph 5.1).
4.1.2.2. Mode "R+TIMER" or “R-TIMER"
)
CAL LOWΩ
.08 Ω
219 mA
5 s
R+
R-
IMER
If during the test a resistance value
R+Timer or R–Timer less than 5Ω was
detected, the instrument (after the set
time has elapsed) emits a double beep
indicating a positive outcome of the
test & displays a screen similar to the
screen alongside.
Duration time of
the test.
Value of the test
current I+ or I-.
The symbols R+ or R- are displayed.
SAVE
SAVING
: The test can be stored pressing the SAVE key twice (refer to
paragraph 5.1).